Skip to main content
ExpertToolkit
Calculators
Health calculators
  • BMI calculator
  • BMR calculator
  • Body fat calculator
  • Ideal weight calculator
Math calculators
  • Percentage calculator
  • Circle area calculator
  • Rectangle area calculator
  • Pythagorean theorem calculator
  • Tip calculator
  • Discount calculator
Converters
Unit conversions
  • Meters to Feet
  • Feet to Meters
  • Inches to Centimeters
  • Centimeters to Inches
  • Miles to Kilometers
  • Kilometers to Miles
  • Kilograms to Pounds
  • Pounds to Kilograms
  • Grams to Ounces
  • Celsius to Fahrenheit
  • Fahrenheit to Celsius
  • Liters to Gallons
  • Gallons to Liters
  • Kilometers/hour to miles/hour
  • Square meters to square feet
Nutrition conversions
  • Apple calories, 1 medium
  • Apple protein, 1 medium
  • Avocado calories, 1 medium
  • Avocado fat, 1 medium
  • Banana calories, 1 medium
  • Banana carbs, 1 medium
  • Beef with egg calories
  • Beef with egg protein
Nutrition comparisons
  • Almonds vs peanut butter
  • Avocado vs olive oil
  • Banana vs apple
  • Blueberries vs strawberries
  • Whole wheat bread vs oats
  • Broccoli vs spinach
  • Chicken breast vs lean beef
  • Raw vs cooked chicken breast
Material density
  • Concrete: 1 yd3 to tons
  • Concrete: 10 yd3 to tons
  • Gravel: 1 yd3 to tons
  • Dry sand: 1 yd3 to tons
  • Topsoil: 1 yd3 to tons
  • Asphalt: 10 tons to yd3
  • Diesel: 100 gal to lb
  • Diesel: 1 bbl to lb
  • Water at 20C: 1 gal to lb
  • Gasoline: 100 gal to lb
Wire gauge
  • 12 AWG, 20A, 50 ft
  • 10 AWG, 30A, 75 ft
  • 120V, 15A, 75 ft
  • 120V, 20A, 50 ft
  • 240V, 30A, 25 ft
  • 240V, 50A, 100 ft
  • 12 AWG vs 10 AWG
  • 10 AWG vs 8 AWG
  • Kitchen outlet, 20A
  • EV charger, 50A at 240V
Formulas
Health
  • BMI formula
Math
  • Percentage formula
  • Circle area formula
Finance
  • Compound Interest formula
  • Mortgage formula
Tables
Length tables
  • Meters to feet table
  • Inches to centimeters table
  • Miles to kilometers table
Weight tables
  • Kilograms to pounds table
Temperature tables
  • Celsius to Fahrenheit table
HomeConvertersWire GaugeWire Gauge for 20A at 50 ft on 120V

Wire Gauge for 20A at 50 ft on 120V — NEC Calculator

For 20A at 50 ft on 120V, use 10 AWG copper. Voltage drop: 2.07%. Per NEC 2023 Table 310.16.

Advanced options — derating, breaker & conduit
10 AWGcopper
Ampacity OKVD 2.07%VD GOVERNS

Long run (50 ft) requires upsizing from 12 AWG to 10 AWG for voltage drop.

Ampacity30Aat 60°C
Voltage drop2.07%2.49V
At load117.5Vreceiving end
Circular mils10,3805.26 mm²
Min for ampacity
12 AWG
6,530 CM
Min for ≤3% VD ← governs
10 AWG
10,380 CM
Breaker size20ANEC 240.6(A)
Wire cost est.~$72100 ft THHN
Conduit size3/4" EMT3 conductors
Ground (EGC)12 AWG CuNEC 250.122
Power loss48W~$58.87/yr
⚠Long run (50 ft) governs — upsized from 12 AWG to 10 AWG for ≤3% VD.

Copper vs Aluminum (for 20A at 50 ft on 120V)

Copper
12 AWG
VD: 3.3% · 3.31 mm²
Aluminum
10 AWG
VD: 3.4% · 5.26 mm²

What wire gauge for 20A at 50 ft on 120V?

For a 20A circuit at 50 ft on 120V, use 10 AWG copper conductor.
At 50 ft, voltage drop is the governing constraint — 12 AWG meets ampacity alone, but the long run requires 10 AWG to stay within 3% voltage drop.

Recommended wire gauge

Voltage drop governs

10 AWG copper

30A ampacity | 2.07% VD | 117.5V at load

Minimum wire by constraint

Required CMs: 7,167 CM. Formula: CM = (2 × K × I × L) / (V × 3%)

ConstraintMin WireCMDetail
Ampacity only12 AWG6,53020A at 60°C
Voltage drop ≤ 3%10 AWG10,3807,167 CM required
Recommended10 AWG10,380VD governs

Wire size by run distance

Distance sensitivity for 20A on 120V at 3% voltage-drop target.

One-way distanceRecommended gaugeVoltage dropReceiving voltageGoverning constraint
25 ft12 AWG1.65%118VAmpacity
50 ft10 AWG2.07%117.5VVoltage drop
75 ft8 AWG1.95%117.7VVoltage drop
100 ft8 AWG2.6%116.9VVoltage drop
150 ft6 AWG2.46%117.1VVoltage drop
200 ft4 AWG2.06%117.5VVoltage drop

Voltage drop by run distance

Visual Analysis1 series6 points

Interactive line view for 1 series and 6 sampled points, built for quick reading and clear comparison.

Trend
Upward
Min
1.65
Max
2.6
Insight
Voltage drop by run distance shows an upward pattern, with a visible peak around 100 ft at 2.6.
1.651.88752.1252.36252.6255075100150200
X-axis: One-way distanceY-axis: Voltage drop (%)

Voltage drop by run distance

Copper vs aluminum for this run

Material comparison uses the same amps, voltage, distance, temperature rating, and voltage-drop limit.

MaterialRecommended gaugeAmpacityVoltage dropResistanceGoverning constraint
copper10 AWG30A2.07%1.24 ohm/kftVoltage drop
aluminum8 AWG30A2.14%1.26 ohm/kftVoltage drop

Protection, conduit, cost, and loss planning

These planning values are generated from the recommended conductor and are not a substitute for field code review.

Planning itemComputed valueWhy it matters
Standard breaker20ANEC 240.6(A): use 20A breaker (next standard size ≥ 20A)
Copper EGC12 AWG CuNEC Table 250.122: 20A OCPD → EGC ≥ 12 AWG Cu (or 10 AWG Al)
Aluminum EGC10 AWG AlUse only where aluminum grounding conductors are permitted and listed.
EMT conduit estimate3/4"3 modeled conductors.
Wire cost estimate$72Approx. 2024 retail THHN pricing. 100 ft total (50 ft × 2 conductors).
Power loss48W420.5 kWh/year at full-duty planning.

Sizing assumptions

Sizing uses copper conductor data, 60C ampacity, single-phase voltage drop, 3% maximum voltage drop, not more than 3 current-carrying conductors, and 30C ambient.
The recommended wire is the larger of the ampacity minimum and the voltage-drop minimum. Long runs can require upsizing even when ampacity alone passes.
Breaker sizing, equipment grounding conductor sizing, conduit estimate, power loss, and cost are computed from the recommended conductor for planning context.

Safety and code review notes

Use the equipment nameplate and local code as the final authority. HVAC, EVSE, motors, continuous loads, and feeders often have extra NEC rules beyond a simple amps-and-distance calculation.
Aluminum conductors require listed AL/CU terminations and installation practices appropriate to the conductor and environment.
This sizing has warnings: Long run (50 ft) governs — upsized from 12 AWG to 10 AWG for ≤3% VD.

Step-by-step wire sizing

Load: 20A at 120V (single-phase), 50 ft, copper at 60°C
Step 1 — Ampacity: find smallest wire where derated ampacity ≥ 20A → 12 AWG (base 20A, no derating)
Step 2 — Voltage drop: allowed VD = 120V × 3% = 3.5999999999999996V
CM = (2 × 12.9 × 20A × 50ft) / 3.5999999999999996V = 7,167 CM → 10 AWG
Step 3 — Recommended: 10 AWG (VD governs)
Breaker: NEC 240.6(A): use 20A breaker (next standard size ≥ 20A)
Ground wire: NEC Table 250.122: 20A OCPD → EGC ≥ 12 AWG Cu (or 10 AWG Al)
Power loss: 48W in run — ~420.5 kWh/yr (~$58.87/yr @ $0.14/kWh)
Cost: ~$0.72/ft × 100 ft = ~$72 (2024 retail THHN)
Conduit: minimum 3/4" EMT for 3 conductors of 10 AWG
Verification: 30A ≥ 20A ✓ | VD 2.07% ≤ 3% ✓

Wire sizing FAQ

Why did the calculator recommend 10 AWG?
10 AWG is needed because voltage drop governs this 50 ft run even though 12 AWG meets ampacity alone.
Does voltage or amperage matter more?
Both matter. Amperage drives ampacity and heat, while voltage and distance drive the voltage-drop percentage seen at the load.
Can aluminum be used instead of copper?
Aluminum may be valid only with AL-rated equipment and code-approved terminations. The material comparison table shows how the recommendation changes when material changes.
What should be checked before installation?
Confirm breaker size, terminal temperature, insulation type, conductor count, raceway fill, ambient conditions, and local code before treating the planning result as final.
Wire Gauge Guides
  • 12 AWG 20A at 50 ft
  • 10 AWG 30A at 75 ft
  • 15A 120V Wire Size
  • 20A 120V Wire Size
  • 30A 240V Wire Size
  • 50A 240V Wire Size
  • 12 AWG vs 10 AWG
  • 10 AWG vs 8 AWG
  • Kitchen Outlet (20A)
  • EV Charger Level 2 (50A)
All Tools
  • Calculators Hub
  • Converters Hub
  • Reference Tables
  • Formulas Hub
Verified Accuracy

All calculations are tested against BIPM, NIST, and NEC 2023 standards.

ExpertToolkit

Calculators, converters, and reference tools designed for clarity, reproducible results, and transparent methodology—built for students, professionals, and everyday use. Built with verified formulas, transparent methodology, and standards-based conversions.

BIPM/NIST Standards Reviewed
Method and AccuracyStandards: reviewed units and formulasMethodologyEditorially maintainedStandards reviewed regularly

For corrections, privacy questions, or broken pages, contact support@experttoolkit.net

Core Hubs

  • Calculators
  • Converters
  • Formulas
  • Reference Tables
  • Connect to AI

Approval Cohort

  • Chicken breast protein
  • Chicken vs turkey breast
  • Top protein foods
  • Concrete yd3 to tons
  • Steel m3 to kg
  • 12 AWG 20A check

Authority

  • Methodology
  • Sources & Standards
  • Rounding Policy
  • Editorial Policy
  • Corrections Policy
  • Disclaimer
  • Sitemap

Legal

  • Privacy Policy
  • Terms of Service
  • Contact
  • Email Support
  • Report an issue
  • Suggest a calculator
  • About Us

© 2026 ExpertToolkit. All rights reserved.

Release 2.5Market: Canada