10 AWG vs 8 AWG — Wire Gauge Comparison
Compare 10 AWG (35A @ 75°C, 10,380 CM) vs 8 AWG (50A @ 75°C, 16,510 CM). Includes copper/aluminum assumptions, ampacity, voltage-drop planning, and NEC/local-code safety notes.
Advanced options — derating, breaker & conduit
Long run (50 ft) requires upsizing from 12 AWG to 10 AWG for voltage drop.
Verify this result
This answer is computed by WireGaugeRegistry.compare (v1.0.0), current for the NEC 2023 edition. The same inputs always produce the same figure and the same fingerprint below, so you can reproduce and cite it.
Standards
- NEC 2023 — Table 310.16 (allowable ampacities)
- ASTM B258-18 — AWG diameters and cross-sectional areas
Assumptions
- Ampacity columncopper, 75°C insulation
- Conditions≤3 current-carrying conductors, 30°C ambient
- Resistance basisDC, ohms per 1,000 ft at 75°C (NEC Ch.9 Table 8)
Inputs & outputs
- in · wireA10awg
- in · wireB8awg
- in · ampacityCu75A35
- in · ampacityCu75B50
- in · areaMm2A5.26
- in · areaMm2B8.37
- in · resistanceCuPerKftA1.24
- in · resistanceCuPerKftB0.778
- out · ampacityDeltaA-15
- out · higherAmpacity8 AWG
- out · areaRatio0.6284
- out · resistanceRatio1.5938
Computation fingerprint (SHA-256)
16d722e7b9bb39c2048860a2632d659838e04d7dac7949eec3ec64af2dd9c891
10 AWG vs 8 AWG: Which is right for your project?
Head-to-head comparison
Source: NEC 2023 Table 310.16. Voltage drop formula: VD = (2 × K × I × L) / CM.
Showing 6 of 10 rows for Specification.
Which gauge wins for this setup?
10 AWG vs 8 AWG must be decided by ampacity, voltage drop, material, terminals, and raceway constraints together.
Voltage drop across common loads
Voltage-drop comparison at 50 ft on 120V. Ampacity still must be checked separately for each load.
Practical impact of choosing the larger gauge
Upsizing can reduce voltage drop and heat, but may raise cost, raceway size, and termination constraints.
Copper and aluminum ampacity comparison
Temperature-rating and material rules can change the final legal choice even when AWG size looks similar.
Wire gauge comparison FAQ
The larger conductor usually lowers resistance and voltage drop, but cost, raceway fill, and terminal compatibility still matter.
8 AWG has the lower modeled voltage drop for 20A at 50 ft.
Only when the replacement satisfies breaker, ampacity, voltage drop, terminal, equipment-label, insulation, and local-code requirements.
This comparison uses 75C for the modeled ampacity. Real terminals and equipment labels decide whether 60C, 75C, or 90C values apply.
Sources & Standards
- National Fire Protection Association. "NFPA 70: National Electrical Code," Table 310.16, 2023 Edition.Allowable ampacities of insulated copper and aluminum conductors (60°C / 75°C / 90°C columns) used in wire sizing
- ASTM International. "Standard Specification for Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors." ASTM B258-18, 2018.AWG conductor diameters and cross-sectional areas used in gauge conversions