Wire Gauge for 15A at 75 ft on 120V — NEC Calculator
For 15A at 75 ft on 120V, use 10 AWG copper. Voltage drop: 2.33%. Per NEC 2023 Table 310.16.
Advanced options — derating, breaker & conduit
Long run (75 ft) requires upsizing from 14 AWG to 10 AWG for voltage drop.
Verify this result
This answer is computed by WireGaugeEngine.sizeWire (v1.0.0), current for the NEC 2023 edition. The same inputs always produce the same figure and the same fingerprint below, so you can reproduce and cite it.
Standards
- NEC 2023 — Table 310.16 (allowable ampacities)
- ASTM B258-18 — AWG diameters and cross-sectional areas
Assumptions
- Conductor materialcopper
- Temperature rating60°C column
- Phasesingle
- Current-carrying conductors3
- Ambient temperature30°C
- Max voltage drop3%
Inputs & outputs
- in · amps15
- in · voltage120
- in · distanceFt75
- in · phasesingle
- in · materialcopper
- in · tempRating60
- in · conductorCount3
- in · ambientTempC30
- in · maxVdropPct3
- out · recommendedWire10 AWG
- out · ampacity30
- out · voltageDropPct2.33
- out · breakerAmps15
- out · groundWire14 AWG Cu
- out · conduit3/4"
- out · vdropDriventrue
Computation fingerprint (SHA-256)
9a89e88fba901ebf7f894aae615b8c50488adf4c52fa76a2b18d7b81a4c3d025
What wire gauge for 15A at 75 ft on 120V?
Recommended wire gauge
Voltage drop governs
10 AWG copper
30A ampacity | 2.33% VD | 117.2V at load
Minimum wire by constraint
Required CMs: 8,063 CM. Formula: CM = (2 × K × I × L) / (V × 3%)
Wire size by run distance
Distance sensitivity for 15A on 120V at 3% voltage-drop target.
Copper vs aluminum for this run
Material comparison uses the same amps, voltage, distance, temperature rating, and voltage-drop limit.
Protection, conduit, cost, and loss planning
These planning values are generated from the recommended conductor and are not a substitute for field code review.
Sizing assumptions
Wire sizing FAQ
10 AWG is needed because voltage drop governs this 75 ft run even though 14 AWG meets ampacity alone.
Both matter. Amperage drives ampacity and heat, while voltage and distance drive the voltage-drop percentage seen at the load.
Aluminum may be valid only with AL-rated equipment and code-approved terminations. The material comparison table shows how the recommendation changes when material changes.
Confirm breaker size, terminal temperature, insulation type, conductor count, raceway fill, ambient conditions, and local code before treating the planning result as final.
Sources & Standards
- National Fire Protection Association. "NFPA 70: National Electrical Code," Table 310.16, 2023 Edition.Allowable ampacities of insulated copper and aluminum conductors (60°C / 75°C / 90°C columns) used in wire sizing
- ASTM International. "Standard Specification for Nominal Diameters and Cross-Sectional Areas of AWG Sizes of Solid Round Wires Used as Electrical Conductors." ASTM B258-18, 2018.AWG conductor diameters and cross-sectional areas used in gauge conversions