Workshop Tool Circuit (30A, 240V) Wire Gauge — NEC 2023 Sizing Guide
30A 240V circuit for table saw, dust collector, or compressor. Use 10 AWG copper. 30A at 75 ft on 240V: 2.33% voltage drop.
10 AWG
copper conductor
2.33%
voltage drop
35A
ampacity
▸ Advanced options — derating, breaker & conduit
10 AWGcopper
Ampacity OKVD 2.33%
10 AWG selected by ampacity (35A ≥ 30A).
35A
Ampacity
at 75°C
2.33%
Voltage drop
5.59V
234.4V
At load
receiving end
10,380
Circular mils
5.26 mm²
Min for ampacity ← governs
10 AWG
10,380 CM
Min for ≤3% VD
10 AWG
10,380 CM
30A
Breaker size
NEC 240.6(A)
~$108
Wire cost est.
150 ft THHN
3/4" EMT
Conduit size
3 conductors
10 AWG Cu
Ground wire (EGC)
NEC 250.122
162W
Power loss
~$198.67/yr
Copper vs Aluminum (for 30A at 75 ft on 240V)
Copper
10 AWG
VD: 2.3% · 5.26 mm²
Aluminum
10 AWG
VD: 3.8% · 5.26 mm²
Workshop Tool Circuit (30A, 240V)
30A 240V circuit for table saw, dust collector, or compressor.
For a 30A load at 75 ft on 240V, use 10 AWG copper.
Workshop — table saw, lathe, air compressor
Required wire gauge
Ampacity governs
10 AWG copper
35A ampacity | 2.33% voltage drop | 240V system
Circuit specifications
NEC 2023 compliant. Min wire for ampacity: 10 AWG. Min wire for 3% VD: 10 AWG.
Preset distance sensitivity
How Workshop Tool Circuit (30A, 240V) sizing changes as one-way run distance changes.
Installation planning checklist
Checklist values are generated from the preset and must be confirmed against the actual equipment and local code before installation.
Copper vs aluminum preset alternatives
Preset alternatives keep the same load, voltage, distance, and voltage-drop target while changing conductor material.
Preset assumptions
This preset models 30A, 240V single-phase, 75 ft one-way, copper conductor, 75C temperature rating, and 3% maximum voltage drop.
Presets are planning shortcuts for common search intents. The equipment nameplate, MCA/MOCP values, continuous-load status, conductor count, ambient temperature, and local amendments can change the final answer.
Common use: Workshop — table saw, lathe, air compressor
Safety and code review notes
Confirm breaker size, conductor insulation, terminal temperature rating, grounding conductor, raceway fill, GFCI/AFCI rules, and wet-location requirements before installation.
For EV chargers, HVAC equipment, motors, spas, detached structures, and service feeders, nameplate and local-code rules can override a generic ampacity calculation.
This preset passes the modeled ampacity and voltage-drop checks under its stated assumptions.
Wire sizing derivation
Load: 30A at 240V (single-phase), 75 ft, copper at 75°C
Step 1 — Ampacity: find smallest wire where derated ampacity ≥ 30A → 10 AWG (base 35A, no derating)
Step 2 — Voltage drop: allowed VD = 240V × 3% = 7.199999999999999V
CM = (2 × 12.9 × 30A × 75ft) / 7.199999999999999V = 8,063 CM → 10 AWG
Step 3 — Recommended: 10 AWG (ampacity governs)
Breaker: NEC 240.6(A): use 30A breaker (next standard size ≥ 30A)
Ground wire: NEC Table 250.122: 30A OCPD → EGC ≥ 10 AWG Cu (or 8 AWG Al)
Power loss: 162W in run — ~1419.1 kWh/yr (~$198.67/yr @ $0.14/kWh)
Cost: ~$0.72/ft × 150 ft = ~$108 (2024 retail THHN)
Conduit: minimum 3/4" EMT for 3 conductors of 10 AWG
Verification: 35A ≥ 30A ✓ | VD 2.33% ≤ 3% ✓
Other common circuits
Kitchen Outlet Circuit (20A, 120V)10 AWG copper20A • 120V • 50ftElectric Dryer (30A, 240V)10 AWG copper30A • 240V • 25ftEV Charger Level 2 (50A, 240V)8 AWG copper50A • 240V • 50ftElectric Range / Oven (50A, 240V)6 AWG copper50A • 240V • 25ftHot Tub / Spa (50A, 240V)8 AWG copper50A • 240V • 60ftSubpanel Feeder (100A, 240V)1 AWG aluminum100A • 240V • 75ft